2 Specifications
The general TraceNet TC Series panel specifications are as given below.
Interior panel operating ambient range -40
◦
F to 140
◦
F (-40
◦
C to 60
◦
C)
Exterior panel operating ambient range -40
◦
F to 131
◦
F (-40
◦
C to 55
◦
C)
Ambient storage range -40
◦
F to 158
◦
F (-40
◦
C to 70
◦
C)
Relative humidity range 0 to 90% Non Condensing
Nominal instrument control voltage 100 to 240 Vac, 50/60 Hz
Temperature sensor types 100 Ohm 3 Wire Platinum RTD
Control temperature range -200
◦
F to 1112
◦
F (-129
◦
C to 600
◦
C)
Maximum power consumption of TCM18 mod-
ule
70 Watts
Current ratings in hazardous (classified) locations based on TraceNet TC Series
panels for up to 72 circuits are as follows
1
:
Maximum Panel Exterior
Ambient (
◦
C)
For: 1 - 36 Circuits For: 37 - 72 Circuits
Maximum Allowable Average Amps per Relay
(Calculated for each side of enclosure)
2
40 22.2 18.0
45 21.0 16.8
50 19.7 15.6
55 18.3 14.3
3 PN 50316_0514