given in the following table.
Tests Description
Perform Self Test The Self Test function (accessed by
pressing the CONFIG key) checks circuit
breaker and output relay functionality.
Perform SCAN Mode Review Operator should do a visual check for out
of range temperatures and low or high
heater and ground/earth leakage current
in the heat tracing circuit(s). No alarms
shall be present on any circuits in the
fourth line of the display screen.
Perform Simulated Ground / Earth Leak-
age Trip Exercise
The TCM18 can simulate a high
ground/earth leakage (accessed by
pressing the CONFIG key) and manually
cause a trip to occur. This allows the
operator to verify that the ground/earth
leakage function is operable.
59 PN 50316_0514