CIRCUIT = 7
MAINTAIN TEMPERATURE
MAINT= 49
◦
C
Figure 12: TCM18 LCD Response
A map of all the information and functions accessible in this manner is summarized
in the following list.
Touch Pad Key Information Display for Circuit in View Mode
MAINTAIN TEMP The display screen provides heat tracing circuit number
and the temperature control set point.
CONTROL BAND The display screen indicates the heat tracing circuit
number, the temperature control band width, and the
programmed control method being employed.
HEATER
CURRENT
The display screen indicates the operating heater cur-
rent and the programmed default power clamp percent-
age in the event of an RTD fault for the circuit number
displayed.
GROUND
CURRENT
The display screen indicates the measured
ground/earth leakage current for the heat tracing
circuit number displayed and the alarm and trip/high-
high alarm activation values.
23 PN 50316_0514