Thermon TESH Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 26
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
INSTALLATION GUIDELINES SERIES HEATING CABLES
PAGE 15
THERMON...The Heat Tracing Specialists
®
TEP0118U-1111
Installation on spectacle blinds
heating cable
300 mm
A
A
Section A-A
For uninsulated spectacle blinds for lines of 2" and larger
Note:
- The heating cables should not touch or cross one
another.
- When prescribed in design apply aluminium tape over
the heating cable.
- Min. bending radius of the heating cable is 5-6 x cable
diameter.
- In each heating cable a loop must be made on the flange
if the pipe diameter allows it. Also extra loops before and
after the flange must be made.
FT fixing tape /
SS tie wire