INSTALLATION GUIDELINES SERIES HEATING CABLES
PAGE 14
THERMON...The Heat Tracing Specialists
®
TEP0118U-1111
Installation on pipe supports, bends and flanges
heating cable
FT fixing tape /
SS tie wire
For lines of 2" and larger
450 mm
heating cable
Note:
- The heating cables should not touch or cross one
another.
- When prescribed in design apply aluminium tape over
the heating cable.
- Min. bending radius of the heating cable is 5-6 x cable
diameter.
- In each heating cable a loop must be made on the flange
if the pipe diameter allows for this.
- It is preferred to isolate the pipe support from the pipes.
FT fixing tape /
SS tie wire
FT fixing tape /
SS tie wire
Note:
Install the cables on the
outer side of the bend as
shown