Item Quantity Description
1 1
Expediter Assembly
Support Cap with O-Ring
Threaded Grommet Compressor
Grommet
Wall Mount Support Base with O-Ring
2 1 Junction Box Lid
3 1 Junction Box Base with O-Ring
4 1 Wall Mount Bracket
5 3 M5 Screws
6 3 Lock Washers
7 1 Terminal Block with DIN Rail
8 1 Junction Box Lid Cord
9 1 Nut
10 1 Power Gland
11 1 Blind Plug
12 2 Wire Pins (per MI Cable Cold Lead)
13 1-2 Banding (Optional, see Steps 1a or 1c)
14 1 XP-1 Bracket (Optional, see Step 1c)
Kit Contents . . .
2
4
3
4
1
5
6
7 8
9
10
11
B-type Tanding (order separately)
B-4: for pipes up to 4"
B-10: for pipes up to 10"
B-21: for pipes up to 21"
13
XP-1-140X80 Stainless Steel
Mounting Bracket
(order separately)
14
Terminator
TM
ZP-MI-WP INSTALLATION PROCEDURES
Wire Pins (per MI cable cold lead,order separately)
12
Certifications/Approvals . . .
1725 II 2 GD Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C FM 10ATEX0058X
IP66 -60°C ≤ Ta ≤ +55°C
Ordinary & Hazardous Locations
IECEx FMG 10.0022X Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C
Warnings . . .
• Duetotheriskofelectricalshock,arcingandrecausedby
product damage or improper usage, installation or mainte-
nance, a ground-fault protection device is required.
• InstallationmustcomplywithThermonrequirementsandbe
installed in accordance with the regulations as per the norm
EN IEC 60079-14 for hazardous areas (where applicable), or
any other applicable national and local codes.
• Installcorrectheatingcablelengthsindicatedinthedesign.
Any deviations from these lengths will result in a change in
outputs.
• Componentapprovalsandperformanceratingsarebased
ontheuseofThermonspeciedpartsonly.
• De-energizeallpowersourcesbeforeopeningenclosure.
• Keependsofheatingcableandkitcomponentsdrybefore
and during installation.
• Minimumbendingradiusofheatingcableis6timesthecable
outer diameter.
Tools Required . . .
Terminator-LN-Tool
(order separately)
3 mm
8 mm
2.5 mm
2
6.0 mm
2
26 mm
28 mm
29 mm
33 mm